Cable Firetuf FT120

Enhanced Fire Resistant Cable
Firetuf FT120 is the ‘enhanced’ fire resistant cable solution for fire alarm, fire detection,emergency voice communication and emergency lighting circuits.

Description
Firetuf FT120

Enhanced Fire Resistant Cable
Firetuf FT120 is the ‘enhanced’ fire resistant cable solution for fire alarm, fire detection,emergency voice communication and emergency lighting circuits.
It meets the requirements of the construction standard BS7629-1, certified by BASEC and also meets the ‘enhanced’ requirements for fire resistance in BS8434-2, certified by LPCB. It is suitable for all ‘enhanced’ applications described in BS5839-1,6,8 & 9 and BS5266-1 and FT120 retains the easy handling advantages of a pliable cable with lower termination costs and no special tool requirements.
Firetuf FT120 – suitable for fire alarm and fire safety applications.
 

Construction

Manufacturing standard BS 7629-1
Conductors Solid or stranded plain annealed copper wire (class 1 or class 2) to BS EN 60228
Conductor (earth) Solid or stranded tinned annealed copper wire (class 1 or class 2) to BS EN 60228
Insulation Enhanced silicone rubber
Electrostatic screen Enhanced close weave glass tape
Binder Enhanced aluminium/polyester laminated tape
Sheath Enhanced thermoplastic Zero Halogen, Low Smoke (OHLS®)
Core Colours Two core: Brown and Blue
Three core: Brown, Black and Grey
Four core: Brown, Black, Grey and Blue
Sheath colour Red or White

 

Characteristics

Voltage rating (U0/U): 300/500V
Operating temp -20°C to 70°C
(the cable should not be installed when either the ambient or cable
temperature is below 0°C)
Min, bending radius 6 x overall diameter of cable
Curent rating Refer to tables 4D2A & 4D2B in BS7671

 

Performance

Circuit integrity BS 5266-1:2011 Clause 8.2.2(b) Enhanced
BS 5839-1:2013 Clause 26.2(e) Enhanced
BS 6387 C, W & Z
BS 8434-2:2003+A2:2009
BS EN 50200 PH120
Smoke emission BS EN 60332-1-2
BS EN 60332-3-24
Flame propagation BS EN 61034-2