Description
Firetuf FT120
Enhanced Fire Resistant Cable
Firetuf FT120 is the ‘enhanced’ fire resistant cable solution for fire alarm, fire detection,emergency voice communication and emergency lighting circuits.
It meets the requirements of the construction standard BS7629-1, certified by BASEC and also meets the ‘enhanced’ requirements for fire resistance in BS8434-2, certified by LPCB. It is suitable for all ‘enhanced’ applications described in BS5839-1,6,8 & 9 and BS5266-1 and FT120 retains the easy handling advantages of a pliable cable with lower termination costs and no special tool requirements.
Firetuf FT120 – suitable for fire alarm and fire safety applications.
Construction
| Manufacturing standard | BS 7629-1 |
| Conductors | Solid or stranded plain annealed copper wire (class 1 or class 2) to BS EN 60228 |
| Conductor (earth) | Solid or stranded tinned annealed copper wire (class 1 or class 2) to BS EN 60228 |
| Insulation | Enhanced silicone rubber |
| Electrostatic screen | Enhanced close weave glass tape |
| Binder | Enhanced aluminium/polyester laminated tape |
| Sheath | Enhanced thermoplastic Zero Halogen, Low Smoke (OHLS®) |
| Core Colours | Two core: Brown and Blue Three core: Brown, Black and Grey Four core: Brown, Black, Grey and Blue |
| Sheath colour | Red or White |
Characteristics
| Voltage rating (U0/U): | 300/500V |
| Operating temp | -20°C to 70°C (the cable should not be installed when either the ambient or cable temperature is below 0°C) |
| Min, bending radius | 6 x overall diameter of cable |
| Curent rating | Refer to tables 4D2A & 4D2B in BS7671 |
Performance
| Circuit integrity | BS 5266-1:2011 Clause 8.2.2(b) Enhanced BS 5839-1:2013 Clause 26.2(e) Enhanced BS 6387 C, W & Z BS 8434-2:2003+A2:2009 BS EN 50200 PH120 |
| Smoke emission | BS EN 60332-1-2 BS EN 60332-3-24 |
| Flame propagation | BS EN 61034-2 |